SIREC D400 Process Recorder

Brand: Siemens AG

The SIREC D400 is a high-end 300 mm x 300 mm XGA display recorder with 16 to 48 analog channels and up to 48 digital channels. 
The wide range of SIREC D products accommodates continuous monitoring, system maintenance, process optimization and troubleshooting requirements.

Specifications

Brand

Display Size and Type

  • 12.1” (30.7 cm) diagonal, color

Resolution

  • XVGA (1024 x 768 pixels)

Screen Saver

  • Set in minutes from 1…720, can be set to dim the screen or to switch off

Brightness Adjustment

  • Adjustable between 10 and 100 %, default set to 80 % brightness.

Backlight Life Time

  • 43 000 hours to half brightness when used at 100 % (67 000 h if used at 80 %), Max. luminosity 400 cd/m²

Display Update Rate

  • Display values updated every second

Status Display

  • A status bar, at the top of the recorder’s screen, displays the realtime icons of the recorder status, such as Recording Time left and alarm active

Communications

  • Ethernet 10/100 base -T with RJ45 connector supporting Modbus/TCP, FTP, Internet, DHCP or fixed IP address. RS-485 Modbus RTU (up to 115200 Baud Rate)

Mathematics

  • Basic Maths include Add, Subtract, Multiply, Divide, Modulo and power. Full Maths and Scripting (option) support up to 100 character free form math expression for each pen. For example SINE, COS, TAN, Log, Parenthesis (eg. A1 + A2), comm variables, free memory, and access to any data item variable (A1, P1, D1 etc.).

Front and Rear USB Ports

  • USB host ports front and rear for data and setup transfers through these ports. External devices (keyboard or mouse), Barcode reader, or external mass storage device. (USB 1.1 compliant)

Standard Screens and Custom Screens

  • Digital values displayed include •Alarms on bars •Engineering units •Pen name •Measuring point number •Tag, time and date •20 character description •Totalised values

Removable Media

  • SD card, supports up to 32 GByte

Local Mass Storage Options

  • USB memory key - must be formatted
  • USB hard drive - up to 120GByte

Internal Data Buffer

  • Non-volatile, 256 GByte (56 million acquisition values) upwards to 3.7GByte (4800 Million points)

Setup and Screens

  • Stored internally on non-volatile memory

Manual Saving

  • Data saving by inserting compact flash card or USB memory stick

Data Saving Period

  • Related to log rate, number of pens, totals and alarms. Each pen is capable of its own independent storage rate (20 ms…60 h)

Data Format

  • Binary encoded format

Recycling Mode

  • Internal memory has FIFO (First In First Out) capability where the newest data over-writes the oldest data

Power Requirements Voltage (VRMS)

  • Power Consumption

Power Requirements Frequency

  • 50/60 Hz

Power Requirements Power Consumption

  • < 60 W

Optional Instrument Power Voltage

  • 20 … 55 Vdc/20 … 30 Vac Power Consumption: < 60 W

NC Common Alarm Relay

  • 2 contacts, normally open when the recorder is powered (no active alarms), rating 24 V, 1 A

Battery

  • Battery backed up for clock, Lithium battery Type 6032, 3.0 V - 10 years life (Recorder powered), 1 year life, typical (Recorder unpowered)

Password Protection

  • Multiple Administrator control of password setup and management with 4 levels of password protection for - Engineer, Supervisor, Technician, and Operator. Up to 50 different users are available. Password protection restricts user entry to the recorder set up and specific screens.

Engineer

  • Highest access to all levels, Supervisor, Technician and Operator

Supervisor

  • 2nd highest level including Technician and Operator access

Technician

  • 3rd level including Operator access

Operator

  • 4th and lowest level of access

Temperature Units

  • °C, °F oder K (Kelvin)

Recorder Identification

  • Status bar: Alternately Displays Recorder ID and Recorder Screen Name. Displays Time and Date.

Clock

  • Accuracy: ± 29 ppm (± 1 minute/ month) at 25° C.

Alarm Set Points

  • 6 per pen integral ”soft” alarm set points easily set by user to announce selected out of limit conditions, user can select if an alarm triggers a change in the screen background colour

Alarm Triggers

  • Alarm triggers can be set for Hi, Lo, Deviation (latched or unlatched) for alarm acknowledgement

Alarm Damping

  • 1 s … 24 h

Hysteresis

  • ± 100 % of pen scale

Common Relay Output

  • 1A , 24 V, can be activated on any alarm

Data Replay Mode

  • Data replay facility on chart displays at normal, fast or slow speeds with zoom and cursor

Display Chart Speeds

  • 1 mm/h
  • 5 mm/h
  • 10 mm/h
  • 20 mm/h
  • 30 mm/h
  • 60 mm/h
  • 120 mm/h
  • 600 mm/h
  • 1200 mm/h
  • 6000 mm/h

Messages Screen

  • The message screen displays system information and records any setup activity that has been changed. It also provides warning and error message updates, lists alarm activity and will display user defined marks on a chart.

CE Conformity (CE Mark)

  • This product conforms with the protection requirements of 2014/35/EC, the Low Voltage Directive, and 2014/30/EC, the EMC Directive. Conformity of this product with any other ”CE Mark” Directive (s) shall not be assumed.

Immunity Product Classification

  • Complies with EN 61326-1: 2013 Class I: Cord Connected, Panel Mounted Industrial Control Equipment with protective earthing (grounding), EN 61010-1: 2010

Enclosure Rating

  • Front panel designed to NEMA 3/IP54 (Optional NEMA 4X/IP66)

Installation Requirements

  • Category II: Overvoltage (EN 61010-1: 2010) Pollution Degree 2

EMC Standards

  • Emissions - EN 61326-1: 2013 Class B Immunity - EN 61326-1: 2013 Industrial Levels

Safety

  • Complies with EN 61010-1: 2010 Panel Mounted Equipment, Terminals must be enclosed within the panel

Number of Inputs

  • 4, 6, 8, 12, 16, 24, 32, 40 or 48 input channels

Input Types

  • mV, V, mA with external shunt (provided as standard), Thermocouple, RTD and ohms

Minimum Input Span

  • Range is fully configurable with span limitation of the operating range selected with 4 % under range to 4 % over-Range capability (50 V Range 2 %)

Burnout (T/C)

  • Active (High or Low), Passive and Health watch/maintenance (option)

Cold Junction Compensation

  • Internal compensation with the ability to manually adjust values, External Input for compensation, External CJC value specified

Input Resolution

  • 0.0015 % (16 Bit ADC)

Current Loop Resistance

  • 10 Ω, Use ± 0.1 % external resistor, Volts > 1 MΩ, All Other > 10 MΩ

T/C and RTD

  • 100 Ω per lead Max. (Cu10 = 15 Ω)

Square Root Extraction

  • Available as standard on every input type

Sensor Compensation

  • Single point and Dual point

Input Sampling Rate

  • Recorder has 2 available slots with up to 8 analog inputs each, the input sampling rate is dependent on actuation type

All Inputs

  • 100 ms (10 Hz), 200 ms (5 Hz), 500 ms (2 Hz)

Fast Sampling

  • 20 ms (50 Hz) - mA, mV, Volts and Ohms only

Linear Scales

  • Engineering units, user definable (10 characters)
  • Normal and Scientific Notation
  • Decimal Point automatic or programmable

Logarithmic Scales

  • Logarithmic Decade limits: -38 min, to +38 max., (recommend up to 20 decades on one screen to ensure clarity)

Input Isolation

  • 300 Vac channel-to-channel, channel-to-ground

Noise Rejection

  • At 50/60 Hz ± 2 %

Common Mode

  • 2 Hz = -120 dB, 5 Hz = -120 dB, 10 Hz = -120 dB

Normal Mode

  • 2 Hz = -85 dB, 5 Hz = -80 dB, 10 Hz = -48 dB

Input Actuation (Linear) mV (DC)

  • -1000 … +1000

Input Actuation (Linear) V (DC)

  • -50 … +50

Input Actuation (Linear) mA

  • 4 … 20, 0 … 20

Input Actuation (Linear) 200 Ω

  • 0 … 200

Input Actuation (Linear) 500 Ω

  • 0 … 500

Input Actuation (Linear) 1000 Ω

  • 0 … 1000

Input Actuation (Linear) 4000 Ω

  • 0 … 4000

Temperature Range

  • -270° to 2,490° C (-454° to 4,515° F)

Logging Method

  • Sample, Average, Min/Max. - can be set independently per pen

Logging Types

  • Continuous, Fuzzy

Logging Rate

  • From 200 ms … 60 h per Pen

Fuzzy Logging

  • A secure data storage technique which delivers data compression ratio of 100: 1 or more, self teaching, storing the data at a variable rate to match the process

Enclosure/Bezel

  • Zinc-Plated Steel case with high impact resistant polycarbonate bezel, scratch resistant lens

Enclosure Rating

  • NEMA 3/IP54 protection rating standard
  • Optional NEMA 4X/IP66 (front face only)

Colour

  • Bezel: Grey

Mounting Panel

  • 55° from the left or right
  • 40° looking down
  • 50° looking up at the recorder display.

Dimensions (W x H x D) in mm

  • Additional 80 mm (3.15”) clearance recommended for a straight type power cable and signal connectors
  • 300 x 300 x 247 (11.34 x 11.34 x 9.72”)

Cutout (W × H) in mm

  • 281 x 281 mm (11.06 x 11.06”)

Weight

  • Maximum 10 kg (22 lb)

Wiring Connections

  • IEC power plug. Removable terminal strip for input and alarm connections

Ambient Temperature

  • 0° C … 50° C (32° F to 122° F)

Relative Humidity (%RH)

  • 10 ... 90

Vibration Frequency (Hz)

  • 0 ... 70

Vibration Acceleration (g)

  • 0.1

Mechanical Shock Acceleration (g)

  • 1

Mechanical Shock Duration (ms)

  • 30

Mounting Position from Vertical Tilted Forward

  • 40°

Mounting Position from Vertical Tilted Backward

  • 65°

Mounting Position from Vertical Tilted to Side (±)

  • 65°

Power Requirements Mains Voltage (Vrms)

  • 100 … 250

Power Requirements Low Voltage AC (Vrms)

  • 20 … 30

Power Requirements DC Voltages

  • 20 … 55

Power Requirements Frequency (Hz)

  • 47 … 63

Power Consumption

  • AC: < 60 W (max)
  • DC: < 60 W (max) . Typical 30 W

Warm Up

  • 30 minutes minimum

Seismic Qualification

  • Complies with IEEE 323-1974 and/or 1983 and IEEE 344-1975 and/or 1987 (optional)

Documentation

show more