Input Tolerance
- Voltage: ± 10 %, Frequency: ± 5 %
Main Circuit
- Three-Phase 2400 V, Integrated 24-Pulse Copper-Wound Isolation Transformer, Multi-Level NPC Medium Voltage IGBT Output
Control Circuit
- Integral to Main Transformer, Includes 460 V for Cooling Fans & PT for 120 V Control
Control Method
- Three-Level Pulse-Width Modulation (PWM) Output Control with Neutral-Point Clamping (NPC)
V/Hz Control
- V/Hz, Sensorless Vector Control, Variable Torque, Closed-Loop Vector Control, & Constant Torque
Frequency Setting
- 4-20 mA, 0 to 10 Vdc Serial Communication Input, & Rotary Encoder Integrated into EOI
Speed Regulation
- Open Loop: Up to 0.5 %, Closed Loop: Up to 0.1 %
Main Protective Functions
- Current Limit, Overcurrent, Overload, Undervoltage, Overvoltage, Ground Fault, CPU Error, & Soft Stall
Overload Current Rating
- 100 % Continuous, 115 % for One Minute Every 20 Minutes
Digital Input
- Ten Discrete Inputs with Programmable Functions
Digital Output
- Ten Available Digital Programmable Outputs
Analog Input
- Three Selectable Inputs Either Currents (0/4 to 20 mA) or Voltage (0 to 10 Vdc)
Analog Output
- Three Selectable Outputs Current (0/4 to 20 mA) or Voltage (0 to 10 Vdc) (Optional up to Eight Max.)
Communication Ports
- Profibus, Modbus RTU & TCP, TOSLINE-S20, TCNet, Ethernet Global Data (EGD), DeviceNet & EtherNet/IP
Display
- 4-Digit, 7-Segment LED Display and 4x20 Character Graphical Plain English Back-Lit LCD Display for Programming, Monitoring & Diagnostics
LED Indicators
- Run (Red)/Stop (Green) & Local (Green)
Keys
- Local/Remote, Enter, Mon/Prg, Esc, Run, & Stop/Reset
Monitoring
- Frequency Command Screen, Multiple Parameters Displayed: Motor Current, Motor Speed, Motor Voltage, DC Voltage, Input Voltage, Output Voltage, Run Time, Output Power, Motor kW, Motor kWH, Motor kVAH, Motor kVAR, & On-Time Control Power
Enclosure
- ANSI-61 Gray, NEMA 1 Ventilated, & IP20 Per IEC 60529, Gasket & Filter, Free-Standing, Front-Access Only
Power Cables
- Top/Bottom Access for Input/Motor Cables
Cooling
- Forced-Air Cooled (Redundant Fan Option)
Standards & Compliances
- NEC, NEMA , UL, cUL, ANSI, & American Recovery & Reinvestment Act Compliant
Ambient Temperature
- 0° to 40° C (50° C Option Available)
Altitude
- 3,281 ft. Above Sea Level (Up to 14,764 ft. Option Available With Derate)
Humidity
- 95 % Max. (Non-Condensing)
Installation
- Indoor, No Direct Sunlight